3. The possibilities of use and the electric installation

The intrinsically safe transmitter can be configured for the following three applications:
1. Transmitter for the combined measurement of relative
humidity and temperature.
Signal working up by the transmitter type HgroFlex.
2. Transmitter for the measurement of relative humidity.
Two wire system,4...20mA
3. Transmitter for the measurement of temperature.
Two wire system,4...20mA
The transmitters are factory programmed for the use as a
humidity and temperature transmitter. The configuration can
be changed by jumpers on the printed circuit.

= Jumper position

Jumper configuration according to block diagram

3.1 Combined transmitter for humidity and temperature measurement (Factory setting)
Signal working up and supply via Zener barrier by the transmitter HygroFlex.
Digtal DIO signal

If other than the Zener barriers Pepperl & Fuchs
Z7222 resp. Z788.H are used, the terminal numbers
may be different!

- Max. cable length between intrinsically safe transmitter
and HygroFlex = 200m
- Cable for the connection of the intrinsically safe
transmitter with the Zener barrier: ET-7018
- Cable for the connection of the Zener barrier with the
HygroFlex: Type AC1617/ZBXXX
- Connection and type of Zener barrier to be used according
to block diagram (Peppel&Fuchs Z722)

AGRO- screw fitting

Schematic diagram

Ex zone

safe zone

intrinsically

safe transmitter

Zener barrier Z722

Cable

AC1617

green

grey

Digital
DIO (%Rh +°C)

Analogue

%Rh

°C

Measurement

of humidity

and temperature

Flange mounting for duct and cable probe
Probe mounting as with duct type, variant B