conduit must also be considered in accordance with NEC requirements. It is suggested that
feeds for four rectifiers (8 wires) and one safety ground wire be run in a one-inch conduit;
however, be sure to follow any local electrical wiring codes.

If the ac input power is provided from a three-phase distribution panel, the circuit breaker
positions should be selected such that the load is balanced as much as possible.