APC DC Power Plant MX28B-1200 User Manual

Page 49

Advertising
background image

Revision B

MX28B-1200 PRODUCT MANUAL

MX28B-1200/2400

43

(Table 6-1. Parameter Locations, Descriptions, and Default Values)

PARAMETER

DESCRIPTION

DISPLAY SCREENS /

DEFAULT SETTINGS

Battery

Alarms

Discharge Alarm {1}

[BATT/SET-ALM]

An alarm that is generated if the battery discharge current
exceeds the programmed battery discharge threshold.

Batt Disc Alm m+

Minor

High Voltage Alarm {1}

[BATT/SET-ALM]

An alarm that is generated if the magnitude of the battery
voltage rises above the high voltage threshold.

Batt HV Alm

m+

Minor

Low Voltage Alarm {1}

[BATT/SET-ALM]

An alarm that is generated if the magnitude of the battery
voltage drops below the low voltage threshold.

Batt LV Alm

m+

Minor

High Temperature Alarm {1}

[BATT/SET-ALM]

An alarm that is generated if the battery temperature exceeds
the high temperature threshold.

Batt HT Alm

m+

Minor

Low Temperature Alarm {1}

[BATT/SET-ALM]

An alarm that is generated if the battery temperature drops
below the low temperature threshold.

Batt LT Alm

m+

Minor

RECTIFIER SETUP

Fail Safe Voltage {1}

[MODULES/RECT/PARAM]

Rectifier default output voltage if communication with the
control unit fails.

Rect Fail Safem+

-54.00 V

Communications Timeout {1}

[MODULES/RECT/PARAM]

The maximum rectifier communications response time
allowed before a communications failure is declared.

Rect Fail Commm+

1 min

Rectifier

Information

NOTE: This information can be viewed for each rectifier
installed by using the horizontal arrow keys.

Rectifier

Description

[MODULES/RECT/INFO]

Displays the model number of the installed rectifier.

Rect 1 Desc

#

MRF28H54

Rectifier

Current

[MODULES/RECT/INFO]

A display of the dc output current for the individual rectifier.

Rect 1 Curr

#

24.9 A

Current

Limit

Alarm

[MODULES/RECT/INFO]

The status will be “ON” if the rectifier has been forced into
its current limited mode.

Rect 1 CL

#

OFF

Standby

Alarm

[MODULES/RECT/INFO]

The status will be “ON” if the control unit is holding the
rectifier in the standby mode.

Rect 1 Stdby

#

OFF

Fan

Fail

Alarm

[MODULES/RECT/INFO]

The status will be “ON” if the rectifier fan has failed.

Rect 1 FF

#

OFF

Rectifier Fault Alarm (RFA)

[MODULES/RECT/INFO]

The status will be on if the rectifier output has failed.

Rect 1 RFA

#

OFF

Rectifier

Alarms

Current Limit Alarm {1}

[MODULES/RECT/SET-ALM]

This alarm indicates that a rectifier has been forced into the
current limited mode.

Rect CL Alm

m+

n of N