MX28B-1200 PRODUCT MANUAL

Revision B

44 MX28B-1200/2400

(Table 6-1. Parameter Locations, Descriptions, and Default Values)

PARAMETER

DESCRIPTION

DISPLAY SCREENS /

DEFAULT SETTINGS

Standby Alarm {1}

[MODULES/RECT/SET-ALM]

This alarm indicates that the control unit is holding a rectifier
in the standby mode.

Rect Stdby Almm+

n of N

Fan Fail Alarm {1}

[MODULES/RECT/SET-ALM]

This alarm indicates that a rectifier fan has failed.

Rect FF Alm

m+

n of N

RFA Alarm {1}

[MODULES/RECT/SET-ALM]

This alarm indicates that a rectifier output has failed.

Rect RFA Alm

m+

n of N

CIRCUIT BREAKER SETUP

Breaker 1 Alias {1}

[MODULES/CIRBKR/ALIAS]

An alternate name (alias) that can be assigned to a circuit
breaker if desired.

Cir Bkr 1

m+

-48V







Breaker 72 Alias {1}

[MODULES/CIRBKR/ALIAS]

An alternate name (alias) that can be assigned to a circuit
breaker if desired.

Cir Bkr 72

m+

-48V

Circuit Breaker Alarms

Breaker 1 Tripped {1}

[MODULES/CIRBKR/SET-ALM]

An alarm that indicates Circuit Breaker 1 is tripped.

Cir Bkr 1 Alm m+

Major







Breaker 72 Tripped {1}

[MODULES/CIRBKR/SET-ALM]

An alarm that indicates Circuit Breaker 24 is tripped.

Cir Bkr 72 Almm+

Major

FUSE SETUP

Fuse 1 Alias {1}

[MODULES/FUSE/ALIAS]

An alternate name (alias) that can be assigned to a Fuse 1 if
desired.

FUSE 1

+

-48V







Fuse 16 Alias {1}

[MODULES/FUSE/ALIAS]

An alternate name (alias) that can be assigned to a Fuse 16 if
desired.

FUSE 16

+

-48V