MX28B-1200 PRODUCT MANUAL

MX28B-1200/2400

45

(Table 6-1. Parameter Locations, Descriptions, and Default Values)

PARAMETER

DESCRIPTION

DISPLAY SCREENS /

DEFAULT SETTINGS

FUSE Fuse Alarms

Fuse 1 Blown {1}

[MODULES/FUSE/SET-ALM]

An alarm that indicates Fuse 1 is blown.

FUSE 1 Alm

m+

Major







Fuse 16 Blown {1}

[MODULES/FUSE/SET-ALM]

An alarm that indicates Fuse 16 is blown.

FUSE 16 Alm

m+

Major

INPUT RELAY SETUP

Input Relay 1 Alias {1}

[SYSTEM/IN-RLY/ALIAS]

An alternate name (alias) can be assigned to the relay if
desired.

In-Rly 1

m+

Input Relay 1







Input Relay 4 Alias {1}

[SYSTEM/IN-RLY/ALIAS]

An alternate name (alias) can be assigned to the relay if
desired.

In-Rly 4

m+

Input Relay 4

Input Relay Alarms

Input Relay 1 {1}

[SYSTEM/IN-RLY/RLY-MAP]

An alarm activated in response to an external contact closure
or opening at the Input Relay 1 connection.

In-Rly 1 Alm

m+

Ignore







Input Relay 4 {1}

[SYSTEM/IN-RLY/RLY-MAP]

An alarm activated in response to an external contact closure
or opening at the Input Relay 4 connection.

In-Rly 4 Alm

m+

Ignore

OUTPUT RELAY SETUP

Output Relay 1 Alias {1}

[SYSTEM/OUT-RLY/ALIAS]

An alternate name (alias) can be assigned to the relay if
desired.

Out-Rly 1

m+

Relay 1







Output Relay 6 Alias {1}

[SYSTEM/OUT-RLY/ALIAS]

An alternate name (alias) can be assigned to the relay if
desired.

Out-Rly 6

m+

Relay 6

Output Relay Minor Alias {1}

[SYSTEM/OUT-RLY/ALIAS]

An alternate name (alias) can be assigned to the relay if
desired.

Relay Minor

m+

Minor