Installation Guide APC BC300 Series 60kW 208/480V UPS

990-1400A

Installation

3.3.6 Communication Interface Board (Option)

Use Class 1 wiring methods.

Figure 9 Communication Interface Board

14
15
2

16
17
4

18
19
6

20
21
8

13 +
25 –

"UPS on" (shown with UPS off)

"Static bypass operation" (shown with static bypass operation off)

"Battery operation" (shown with battery operation off)

"Battery low warning" (shown with "battery low" warning off)

Remote UPS shut down input (3.5 - 25 VDC pulse for 1 second minimum)

Serial Port
RS232

Serial Port
0-20 mA current loop

X003 25 PIN SUB D MALE

X004 25 PIN SUB D MALE

X005 25 PIN SUB D FEMALE

Relay Contacts: 30VAC, 60 VDC
Maximum 0.5 A, minimum 0.05 mA

X002

X001

X003

X004

X005

Communication

Interface Board