Technical specifications – APC BC300 User Manual
Page 35

Technical Specifications
990-1400A
Installation Guide APC BC300 Series 60kW 208/480V UPS
35
7.2
Battery Specifications
7.3
Dimensions/Weight
60kW
Nominal DC current - Amps
300
UL rating of terminal blocks - AWG
a
a.Terminal block has two positive and two negative
8 mm (=5/16”) studs, hardware provided. Lug re-
quired.
Conductor size may vary based on installation re-
quirements. Size all conductors per applicable
codes.
14 - 2/0
Nominal DC voltage
216
Nominal number of cells
108
Factory-set float charge voltage
b
b.Adjust the float charge voltage setting according
to the battery manufacturer’s recommendations.
246
Charger current limit - Amps
c
c.Programmable to lower level.
30
Inverter efficiency -% 100% load
75% load
50% load
25% load
92
92
90
87
BC300 Series UPS
60kW
Height
59.1 inches
Width
39.4 inches
Depth
31.7 inches
Weight 2214
lbs