Click on Operation button, and under the Modulation Menu, set

the required Firing rate (High/Low) by setting the RPM.

On the Firing Rate page, set the Firing rate RPM by selecting the

Manual in Run check box.

ADJUSTMENT

There must be sufficient load to operate the boiler at high fire to

perform the following adjustments. Start the boiler and observe

proper operating parameters for the system.
Required Tools:

• TORX

®

T40 or 5 mm hex wrench

• 3 mm or 7/64 inch hex wrench
• Combustion analyzer

These boilers are equipped with a combined gas/air control

and gas safety shut off control valves. The valve functions in

parallel with the variable speed combustion blower to supply

the correct gas air ratio for optimum performance and efficiency.

The combustion blower speed is controlled automatically and

determines the amount of negative pressure experienced by the

gas safety shut off/control valves. The gas/air regulator adjusts

gas flow to maintain the proper pressure at the outlet nozzle of

the associated valve.

SETTING OF THE TEST MODE

On the Burner Home screen, select any individual boiler which

will guide to Burner Information screen.

FIGURE 42. BURNER HOME SCREEN

FIGURE 43. BURNER INFORMATION SCREEN

FIGURE 44. OPERATION SCREEN

FIGURE 45. FIRING RATE PAGE