A.O. Smith 3400 User Manual

Page 64

Advertising
background image

64

CODE

DESCRIPTION

RECOMMENDED TROUBLESHOOTING OF

LOCKOUT CODES

NOTE

149

Flame detected

OEM Specific

1. Holds if flame detected during Safe Start check

up to Flame Establishing period.

H or L

150

Flame not detected

OEM Specific

1. Sequence returns to standby and restarts

sequence at the beginning of Purge after the HF

switch opens. If flame detected during Safe Start

check up to Flame Establishing period.

H

151

High fire switch ON

OEM Specific

1. Check wiring and correct any potential wiring

errors.

2. Check High Fire Switch to assure proper function

(not welded or jumpered).

3. Manually drive the motor to the High Fire position

and adjust the HF switch while in this position

and verify voltage through the switch to the HFS

input with a voltmeter.

4. If steps 1-3 are correct and the fault persists,

replace the module.

H or L

152

Combustion pressure ON

OEM Specific

1. Check wiring and correct any errors.

2. Inspect the Combustion Pressure Switch to make

sure it is working correctly.

3. Reset and sequence the relay module.

4. During STANDBY and PREPURGE, measure

the voltage between Terminal J6-5 and L2 (N).

Supply voltage should be present. If not, the

lockout switch is defective and needs replacing.

5. If the fault persists, replace the relay module.

H or L

153

Combustion pressure Off

H or L

154

Purge Fan switch On

OEM Specific

1. Purge fan switch is on when it should be off.

H or L

155

Purge Fan switch Off

H

156

Combustion pressure and Flame ON

OEM Specific

1. Check that flame is not present in the combustion

chamber. Correct any errors.

2. Make sure that the flame detector is wired to the

correct terminal.

3. Make sure the F & G wires are protected from

stray noise pickup.

4. Reset and sequence the module, if code

reappears, replace the flame detector.

H or L

157

Combustion pressure and Flame OFF

L

158

Main valve ON

OEM Specific

1. Check Main Valve terminal wiring and correct any

errors.

2. Reset and sequence the module. If fault persist,

replace the module.

L

159

Main valve OFF

L

160

Ignition ON

OEM Specific

1. Check Ignition terminal wiring and correct any

errors.

2. Reset and sequence the module. If fault persist,

replace the module.

L

161

Ignition OFF

L

162

Pilot valve ON

OEM Specific

1. Check Pilot Valve terminal wiring and correct any

errors.

2. Reset and sequence the module. If fault persist,

replace the module.

L

163

Pilot valve OFF

L