CODE

DESCRIPTION

RECOMMENDED TROUBLESHOOTING OF

LOCKOUT CODES

NOTE

164

Block intake ON

OEM Specific

1. Check wiring and correct any errors.

2. Inspect the Block Intake Switch to make sure it is

working correctly.

3. Reset and sequence the module.

4. During Standby and Purge, measure the voltage

across the switch. Supply voltage should

be present. If not, the Block Intake Switch is

defective and needs replacing.

5. If the fault persists, replace the relay module.

L

165

Block intake OFF

L

166-171 RESERVED

Feedback

172

Main relay feedback incorrect

Internal Fault.

1. Reset Module.

2. If fault repeats, replace module.

L

173

Pilot relay feedback incorrect

L

174

Safety relay feedback incorrect

L

175

Safety relay open

L

176

Main relay ON at safe start check

L

177

Pilot relay ON at safe start check

L

178

Safety relay ON at safe start check

L

179-183 RESERVED

Parameter Faults

184

Invalid BLOWER/HSI output setting

1. Return to Configuration mode and recheck

selected parameters, reverify and reset module.

2. If fault repeats, verify electrical grounding.

3. If fault repeats, replace module.

L

185

Invalid Delta T limit enable setting

L

186

Invalid Delta T limit response setting

L

187

Invalid DHW high limit enable setting

L

188

Invalid DHW high limit response setting

L

189

Invalid Flame sensor type setting

L

190

Invalid interrupted air switch enable setting

L

191

Invalid interrupted air switch start check enable

setting

L

192

Invalid igniter on during setting

L

193

Invalid ignite failure delay setting

L

194

Invalid ignite failure response setting

1. Return to Configuration mode and recheck

selected parameters, reverify and reset module.

2. If fault repeats, verify electrical grounding.

3. If fault repeats, replace module.

L

195

Invalid ignite failure retries setting

L

196

Invalid ignition source setting

L

197

Invalid interlock open response setting

L

198

Invalid interlock start check setting

L

199

Invalid LCI enable setting

L

200

Invalid lightoff rate setting

L

201

Invalid lightoff rate proving setting

L

202

Invalid Main Flame Establishing Period time

L

203

Invalid MFEP flame failure response setting

L

204

Invalid NTC sensor type setting

L

205

Invalid Outlet high limit response setting

L

206

Invalid Pilot Flame Establishing Period setting

L

207

Invalid PII enable setting

L

208

Invalid pilot test hold setting

L

209

Invalid Pilot type setting

L

210

Invalid Postpurge time setting

L

211

Invalid Power up with lockout setting

L

Advertising
This manual is related to the following products: