Installation, English, How to install the unit – LG LP155CED1 User Manual

Page 11: Notice

Advertising
background image

Owner’s Manual 11

ENGLISH

Installation

How to Install the Unit

Installation

406 mm

(16")

406 mm

(16")

1,066 mm

(42")

1066 mm

(42")

318 mm
(12

1

/

2

")

349

1

/

4

mm

(13

3

/

4

")

505 mm

(20")

Over 20"

HEAT

RADIATION

WALL

WALL

INSULATION

SLEEVE

INTAKE

AIR

COOLED

AIR

1/4" Bubble

of the level

Front

Insulation Strip

Rear

Sleeve

280 mm

(11")

• There are sharp edges that can cause serious cuts.
• When lifting the air conditioner, it is HEAVY.

Use 2 people to lift.

For existing sleeve, you should measure the wall
sleeve dimensions.
You can install the new air conditioner according to
these installation instructions to achieve the best
performence. All wall sleeves used to mount the new air
conditioner must be in good structural condition and
have the rear grille that securely attaches to the sleeve
or the flange of the sleeve to secure the new air
conditioner.

• To avoid vibration and noise, make sure the unit is

installed securely and firmly.

When installing the sleeve, make certain there is
nothing within 20" of the back that would interfere with
heat radiation and exhaust air flow.

To maintain the best

performance of the LG PTAC,
an insulation strip must be
attached. The insulation strip
is provided with the box.
Refer to the diagram below.

1) Take out the insulation strip from the upper packing.

2) Attach the insulation strip onto the rear upper side of

the wall sleeve.

3) If anyone would like to improve unit energy efficiency,

it is recommended the change of outside grille for an
unit protection and an addition of a plastic rear grille.
(This is optional.)

NOTICE

Dimension of air conditioner

Dimension of sleeve assembly (optional)

Advertising