English, Room air conditioner voltage limits – LG LP155CED1 User Manual

Page 25

Advertising
background image

Owner’s Manual 25

ENGLISH

Maintenance and Service

NAME PLATE RATING

MINIMUM

MAXIMUM

208/230 V

187 V

253 V

265 V

238 V

292 V

ROOM AIR CONDITIONER VOLTAGE LIMITS

COMPLAINT

CAUSE

REMEDY

Voltage

Overload

Fan motor

Condenser air flow
restriction

Condenser fins
(damaged)

Capacitor

Wiring

Refrigerating system

Air filter

Exhaust damper door

Unit undersized

Cross flow fan

Copper tubing

• Check the voltage. See the limits on the preceding

page. If not within limits, call an electrician.

• Check overload, if externally mounted.

Replace if open. (If the compressor temperature is
high, remove the overload, cool, and retest.)

• If not running, determine the cause. Replace if

required.

• Remove the cabinet. inspect the interior surface of the

condenser; if restricted, clean carefully with a vacuum
cleaner (do not damage fins) or brush. Clean the
interior base before reassembling.

• If condenser fins are closed over a large area on the

coil surface, head pressures will increase, causing the
compressor to cycle. Straighten the fins or replace the
coil.

• Test capacitor.

• Check the terminals. If loose, repair or replace.

• Check the system for a restriction.

• If restricted, clean or replace.

• Close if open.

• Determine if the unit is properly sized for the area to

be cooled.

• Check the set screw or clamp. If loose or missing,

correct. If the blower or fan is hitting air guide,
rearrange the air handling parts.

• Carefully rearrange tubing not to contact, compressor,

shroud, and barrier.

Compressor

cycles on

overload.

Insufficient

cooling or heating

Excessive noise.

Advertising