Troubleshooting, Agent does not install on red hat itanium, Attached device communication errors appear – HP UPS Management Modules User Manual

Page 91: Attached device did not shut down gracefully, Battery test did not run

Advertising
background image

Troubleshooting 91

Troubleshooting

ASCII character sequence Esc+Shift+9 directs all
serial communication to the iLO port for the HP
ProLiant DL380 G4

Action: Disable iLO.

Agent does not install on Red Hat Itanium®

Action:

1.

Install the ia32* file for your operating system from the supplementary disc.

2.

Install the appropriate library files for your operating system from the compact layer in the following
order:

a.

Install the glibc* library file.

b.

Install the zlib* library file.

3.

Install the agent using the Linux installation script ("

Installing the agent using the installation script

"

on page

35

).

-or-
Install the agent using the Linux silent installation method ("

Installing the agent using the silent

installation method

" on page

36

).

Attached device communication errors appear

Action: Use the device IP address, not the host name, when attaching devices.

Attached device did not shut down gracefully

Action: Be sure the shutdown settings do not exceed the UPS runtime.

Battery Test did not run

Possible Cause: The UPS is On Battery.
Action: The UPS must be in a certain state before the battery test runs. For more information, refer to the
section, "Parameters menu option ("

Parameters menu

" on page

52

)."