Troubleshooting 94

Event notifications are not being sent

Action: While email and SNMP trap notifications must be set up on their respective screens, notifications
must also be enabled per event on the Event Notifications screen ("

Event Notifications menu

" on page

67

).

FTP error messages appear when connecting
through Linux

Symptom: When connecting to FTP through Linux, error messages about bad commands appear.
Action: The user can log in although the error messages appear.

Flash update fails over a serial connection

Action: Disable any serial port being configured during the flash update, such as iLO, or use an FTP
connection.

HP SIM lists a discovered UPS as Unmanaged in the
System Type column

Action:

1.

Delete the discovered UPS from HP SIM.

2.

Using the management module web interface, add the HP SIM server as a Manager on the SNMP
Managers tab (on page

65

).

3.

Rediscover the UPS in HP SIM.

HPFlash does not install image.bin on a Pentium III

Symptom: The image.bin file is not installed on a Pentium III during a serial upgrade.
Possible Cause: The minimum hardware requirement for HPFlash is Pentium 4.
Action: Be sure that the hardware meets the minimum HPFlash requirements.

Initiate Battery Test Command Has Been Sent
message not displayed

Action: View the results of the battery test on the Application Log screen ("

Application Log menu

" on page

58

).