Error led illuminates or flashes, Error during agent installation – HP UPS Management Modules User Manual

Page 93

Advertising
background image

Troubleshooting 93

Install an SSL certificate that Internet Explorer recognizes.
-or-

Click Continue to this website (not recommended) to ignore the security warning.

Email notifications are not received from an HP-UX
server

Action: Add the IP address of the email server to the host file of the computer running the UPS Power
Protection Agent.

Error LED illuminates or flashes

Action: Press the Reset button on the management module front panel. If the problem persists, contact an
authorized service provider.
The following table lists the error conditions associated with the management module LED.

Test

LED flash error code

Description

1

Permanently on

DRAM failure

2

2 flashes

DMA Mem to Mem error

3

3 flashes

IRQ error

4

4 flashes

Ethernet error

5

5 flashes

Serial loop back error

6

6 flashes

RTC error

Error during agent installation

Symptom: An error occurs while installing the agent on servers with Red Hat 5.0.
Possible cause: Security enhanced Linux is enabled.
Action: Run the following commands:

1.

#chcon –t textrel_shlib_t ‘/usr/local/DevMan/DMSetup'

2.

/etc/init.d# ./DevMan setup

3.

#chcon –t textrel_shlib_t ‘/usr/local/DevMan/DevManRA'

Event notification messages do not appear on
console screen

Action: If you are using SLES 9, upgrade the KDE or use a different desktop, such as GNOME.