Stacking options – Outback Power Systems VFX Series International Programming Manual User Manual

Page 24

Advertising
background image

23

STACKING OPTIONS

OutBack International Series FXs can be stacked in one of two confi gurations:

1. OutBack Parallel

2. 3-Phase

NOTE: Although stacking 10 FXs is possible, OutBack’s AC hardware only accommodates confi gura-
tions of two, four, or eight FXs. A system with eight FXs would require two AC Input/Output Bypass
(IOB) Breaker Kits or installing an external manual bypass; ten FXs would require three IOB kits or an
external manual bypass.

1. Outback Parallel

• 2-10 FXs are wired to the same 230 VAC output leg or phase.

• The Slave FXs can be programmed to remain at diff erent power levels (Silent or On depending on

the need) to save energy; the Slaves will come on when the power demand requires them.

• This power-saving system is fully automatic and works with or without a MATE connected to the

system, although a MATE is required to program the components. Without a MATE, the user cannot

reprogram.

• The AC input (generator or grid) must be 230VAC.

3 kW 230 VAC

3 kW 230 VAC

3 kW 230 VAC

9 kW

230 VAC

LOAD

Advertising