seQuenCe of operation flow Chart

Description of this flow chart can be found in the “SeqUeNCe OF OPerATION” section found on page 26.

Thermostat calls for heat

Switch power on to unit

Blower engages Prover Switch

After 30 seconds, Ignition

Control provides power to

Spark Igniter and opens Gas

Valve

Ignition Control maintains spark for up

to 4 seconds and monitors Flame

Sensor to determine if Burner is lit

Does Burner

light?

Ignition Control changes Blower from

low speed to high speed after 5 seconds

Ignition Control monitors

flame signal

Thermostat is satisfied

Blower – off; Blower Prover – opens

Ignition Control – off; Gas Valve – closes

Wait 15 minutes.

Blower runs at

low speed

Is this the third loss

of flame signal?

Is this the third

ignition trial?

Loss of flame signal?

YES

YES

NO

NO

Gas Valve – off

Gas Valve – off

NO

NO

YES

YES

UGB sends PWM signal to Blower to

start the blower at high purge speed

20 seconds later blower

runs at low igniƟon speed

figure 24.