Draining and flushing, Deliming solvents – State SBL95 250NE A User Manual

Page 29

Advertising
background image

29

draining and flushing

Burn harzard.

Hot water discharge.

Keep hands clear of drain

valve discharge.

It is recommended that the water heater storage tank be drained

and flushed every 6 months to reduce sediment buildup. The

water heater should be drained if being shut down during freezing

temperatures.

to drain the water heater storage tank:

1. Turn off the electrical supply to the water heater.
2. Turn off the gas supply at the Main Gas Shutoff Valve if

the water heater is going to be shut down for an extended

period.

3. ensure the cold water inlet valve is open.
4. Open a nearby hot water faucet and let the water run until

the water is no longer hot.

5. Close the cold water inlet valve to the water heater.
6. Connect a hose to the water heater drain valve and terminate

it to an adequate drain.

7. Open the water heater drain valve and allow all the water to

drain from the storage tank.

8. Close the water heater drain valve when all water in the

storage tank has drained.

9. Close the hot water faucet opened in Step 4.
10. If the water heater is going to be shut down for an extended

period, the drain valve should be left open.

to flush the water heater storage tank:

1. Turn off the electrical supply to the water heater.
2. ensure the cold water inlet valve is open.
3. Open a nearby hot water faucet and let the water run until

the water is no longer hot. Then close the hot water faucet.

4. Connect a hose to the drain valve and terminate it to an

adequate drain.

5. ensure the drain hose is secured before and during the

entire flushing procedure. Flushing is performed with system

water pressure applied to the water heater.

6. Open the water heater drain valve to flush the storage tank.
7. Flush the water heater storage tank to remove sediment and

allow the water to flow until it runs clean.

8. Close the water heater drain valve when flushing is completed.
9. remove the drain hose.
10. Fill the water heater - see Filling The Water Heater in this manual.
11. Turn on the electrical supply to place the water heater back

in operation.

12. Turn on the gas supply to the water heater at the Main Gas

Shutoff Valve.

13. Allow the water heater to complete several heating cycles to

ensure it is operating properly.

periodiC remoVal of lime deposits from

tank type CommerCial water heaters

The amount of calcium carbonate (lime) released from water is

in direct proportion to water temperature and usage, see chart.

The higher the water temperature or water usage, the more lime

deposits are dropped out of the water. This is the lime scale

which forms in pipes, heaters and on cooking utensils.
lime accumulation may affect the life of equipment, the efficiency

of the heater, and fuel consumption characteristics. The usage of

water softening equipment greatly reduces the hardness of the

water. However, this equipment does not always remove all of

the hardness (lime). For this reason it is recommended that a

regular schedule for deliming be maintained.
The time between cleaning will vary from weeks to years

depending upon water conditions and usage.
The depth of lime buildup should be measured periodically.

Heaters equipped with cleanouts will have about 2" of lime

buildup when the level of lime has reached the bottom of the

cleanout opening. A schedule for deliming should then be set up

based on the amount of time it would take for a 1" buildup of lime.

It is recommended that the water heater initially be inspected

after 6 months.

example 1:

Initial inspection after 6 months shows 1/2" of lime accumulation.

Therefore, the heater should be delimed once a year.

example 2:

Initial inspection after 6 months shows 2" of lime accumulation.

Therefore, the heater should be delimed every 3 months.

figure 26.

deliming solVents

UN•lIMe is recommended for deliming. UN•lIMe is a patented

food grade acid which is safe to handle and does not create the

harmful fumes which are associated with other products.
UN•lIMe may be obtained from your dealer, distributor or water

heater manufacturer. Order Part Number 9005416105, 1 gallon,

packed 4 gallons per case or Part Number 9005417105, 5 gallon

container.

Advertising
This manual is related to the following products: