Wires (awg 15 ), stranded wires recommended – Vaisala HMP140 User Manual
Page 10
Advertising
![background image](/manuals/408438/10/background.png)
HMP140A SERIES
Operating Manual
U175en-1.5
6
1999-12-08
3.3
Electrical connections
The wiring can be done in either of the two ways shown in Figure 3.3.
mounting on a juction box
surface mount
Vs
RHout
SHIELD
Tout
GND
W
W
BI9
U
RXW
TCD@G9
SC
RXW
W
6
6
BI9
U
RXW
TCD@G9
SC
RXW
W
@yrp vphyÃprpvГГ6Г)
@yrp vphyÃprpvÃÃWÃ)
W
W
Figure 3.3
Electrical connections
Outputs
0...20 mA (4...20 mA)
20...35 VDC
17...24 VAC
min.
50
)
(
12
ohm
R
L
+
VDC
0...1 V
9...35 VDC
9...24 VAC
0...5 V
15...35 VDC
12...24 VAC
0...10 V
20...35 VDC
16...24 VAC
Current consumption
6...10 mA + output currents
Electrical connections
screw terminals for 0.5 - 1.5 mm
2
wires (AWG
15...20), stranded wires recommended