HMP140A SERIES
Operating Manual

U175en-1.5

8

1999-12-08

3.6

Connection to an AC supply

The HMP140A transmitters can also be connected to an AC supply without an
external rectifier. However, when two or more transmitters are connected to
one 24 VAC transformer, a common loop is formed and there is an increased
risk of a short-circuit. To avoid this, always use separate floating supply for
each transmitter (see Figure 3.6 A). However, if several transmitters have to
share one transformer, always connect the phase (

) to + connector in each

transmitter (see Figure 3.6 B).

HMP140 transmitter

HMP140 transmitter

Controller

shared
common line

HMP140 transmitter

HMP140 transmitter

Controller

s

u

pply vol

ta

g

e

s

ign

a

l out

put

sup

p

ly

volt

age

s

ig

n

al

ou

tp

u

t

B) COMMON LOOP FORMED - NOT RECOMMENDED!

A) NO COMMON LOOP FORMED - RECOMMENDED

s

uppl

y

v

o

lt

age

si

gnal

out

put

su

p

p

ly vo

lt

a

g

e

si

gna

l out

put

Figure 3.6

Connecting the transmitters to a 24 VAC supply