WS425 NMEA Extended Profile (v. 0183)

When the WS425 A/B NMEA Extended profile is selected, you
can set WMT700 to send messages based on the configured
automatic message interval or poll data using the $WIP
command.

Configurable Parameters

Table 47 below lists the configurable parameters and their
allowed and default values for the WS425 A/B NMEA Extended
profile.

Table 47

Configurable Parameters for WS425 A/B
NMEA Extended Profile

Parameter

Default
Value

Profile-Specific
Allowed Values

Description

address

A

String with 1 character

Address for WMT700

autoInt

1

0.25 ... 1000
Resolution: 0.25

Automatic message interval in seconds. Do
not select a message interval that is shorter
than the time it takes to send a data message

autoPort

2

1 = COM1 port
2 = COM2 port

Serial port to which WMT700 sends automatic
data messages

autoSend

15

0 = Automatic
messages disabled
15 = NMEA automatic
data message

Automatic data message number. Selects the
data message format for automatic messages

com1_protocol 0*

5 = WS425 A/B NMEA
Extended

Profile for serial port COM1

com2_protocol

5

5 = WS425 A/B NMEA
Extended

Profile for serial port COM2

com2_interf

N/A**

0 = RS-485
1 = RS-422
3 = RS-232

Interface for serial port COM2

wndAvg

3

0.25 … 3600
Resolution: 0.25

Averaging time for wind measurement in
seconds

wndOrientation 0

0 = Array facing up
1 = Array facing down

Orientation of the array of WMT700

wndUnit

0**

0 = Meters per second
1 = Miles per hour
2 = Kilometers per hour
3 = Knots

Wind speed unit

wndVector

0

0 = Scalar averaging

Wind averaging method

* COM1 service port is always by default 0 - WMT700 protocol. This can be
changed using serial commands if COM1 is needed for protocol-specific
communication.
** Wind speed unit and COM2 digital communication interface are defined in
the order form. Default setting may be any of the allowed options, and it can be
verified from the unit’s configuration code.