PV100

Valve Controller

Mode 3 -

AIN is not used.

DIN1 enables forward direction.

DIN2 enables reverse direction.

When DIN3 is off, the speed is set to the low speed output value.

When DIN3 is on, the speed is set to the maximum output value.

Reverse override supersedes forward override.

Mode

4

-

Exactly the same function as Mode

0

, except the enable input (DIN1) enables the module.

0 to 100% input controls coil A current promotionally.

0 to -100% input controls coil B current proportionally.

Digital inputs provide forward and reverse overrides.

Forward override supersedes reverse override.

Mode

5

-

Exactly the same function as Mode

1

, except the enable input (DIN1) enables the module.

0 to 100% input enables coil A output.

0 to -100% input enables coil B output.

When the high speed input (DIN3) is off, the speed is set to the minimum output value.

When the high speed input (DIN3) is on, the speed is set to the maximum output value.

Mode

6

-

Exactly the same function as Mode

2,

except the enable input (DIN1) enables the module.

By default, it enables coil A in forward direction.

The speed is controlled proportionally by the analog input of 0 to 100% only.

DIN2 enables coil B in reverse direction.

Reverse override supersedes forward override.

Mode

7

-

Exactly the same function as Mode

3,

except the enable input (DIN1) enables the module.

DIN2 enables reverse direction.

When DIN3 is off, the speed is set to the low speed output value.

When DIN3 is on, the speed is set to the maximum output value.

Reverse override supersedes forward override.