DN-4786:A1 • 1/7/10 — Page 1 of 2

B401BH and B401BHA

Conventional Bases with Sounder

Conventional Initiating Devices

DN-4786:A1 • I-130

General

The System Sensor

B401BH(A) Base with Sounder is used

with conventional 400 Series two-wire plug-in smoke detec-

tors. Refer to the associated control panel manual for more

information on detector heads.

NOTE: Only compatible UL/ULC-approved smoke detectors may
be used with the B401BH(A).

Features

• Sound output greater than 90 dBA measured in anechoic

room at 10 feet (3.048 m), 24 volts. 85 dBA minimum mea-

sured in a UL reverberant room.

• An alarm delay of approximately 10 seconds is built into

the B401BH(A). This delay is present whether the control

signal comes from the sensor or from reversing the exter-

nal power supply polarity.

Applications

The B401BH(A) base is intended for use with conventional

plug-in systems. See systems literature for maximum allow-

able number of units per loop.

Construction and Operation

The B401BH(A) requires an external 24 VDC supply with

reverse polarity capability. The connections of the external

supply (terminals 1 and 2) and the communication/initiating

loop (terminals 3, 4, and 5) are isolated in the B401BH(A) to

prevent electrical interaction between them.

NOTE: When not used as a supplementary evacuation system,
the external 24 VDC supply shall be treated as a component of the
main power supply system and shall fall under the requirements of
the main power supply system per NFPA 72.

When the detector head’s visible LEDs are latched ON for

approximately 10 seconds, the base horn sounds. A loop of

horns can be made to sound with the polarity reversal of the

external supply.

Installation

NFPA 72 and NEMA guidelines should be observed. For
installation in Canada,

refer to CAN/ULC S524, Standard

for the Installation of Fire Alarm Systems and CEC Part 1,

Sec. 32.
Units must be mounted directly to a 4.0" (101.6 mm) square

electrical box, minimum 1.5" (38.1 mm) deep, using the sup-

plied mounting kit. A maximum space of 0.125" (3.175 mm)

from outside edge of electrical box to the inside edge of the

drywall or ceiling tile is allowable.
A flangeless plug-in base is used to attach detectors to the

B401BH(A) base with sounder.
Before installing detectors, please read Guide for Proper Use
of System Smoke Detectors

, document number 156-407-00,

which provides detailed information on detector spacing,

placement, zoning, wiring, and special applications.

B601BH(A) TERMINALS:

1. External Supply Positive (+)
2. External Supply Negative (–)
3. Negative (–) V In
4. Positive (+) V In and V Out
5. Negative (–) V Out

NOTE: Terminals 3, 4, and 5 are used for the communication/initi-
ating circuit.

Specifications

Base diameter: 6.0" (152.4 mm).
Base height (less base & sensor): 0.75" (19.05 mm).
Weight: 0.3 lbs. (140 grams).
Operating temperature range: 14°F to 140°F (–10°C to

+60°C).
Operating humidity range: 10% to 95% relative humidity,

non condensing.
Sounder in UL reverberant room: 85 dBA minimum.
Sounder in anechoic room: > 90 dBA @ 10 feet (3 m), 24

volts.

Electrical Ratings

Wiring: Two-wire.

EXTERNAL SUPPLY:

Voltage: 17 to 32 VDC.
Standby current: 1.0 mA maximum.
Alarm current: 15 mA maximum.

4786pho1.jpg

B401BH sounder assembly, shown

with a 2541 photo detector