DN-1154:A • 6/4/08 — Page 1 of 4

1451

2-Wire and 4-Wire
Ionization Smoke Detector

Conventional Initiating Devices

DN-1154:A • I-110

General

The System Sensor 400 Series plug-in ionization smoke

detectors respond quickly to both fast flaming and slow smol-

dering fires as required by UL 268. Unipolar dual chamber

sensor has the sensitivity needed to quickly detect smoke, and

the stability needed to avoid false alarms.

Features

• Unique dual unipolar sensor:

Provides exceptional stability.
Factory preset at 1.9% nominal sensitivity.
Stable operation up to 1,200 feet per minute (6 meters per

second) air velocities.

• Removable cover for field cleaning.
• Two visible LEDs “blink” in standby.
• Sealed against dirt, insects, and back pressure.
• Three-year limited warranty.
• Field metering of detector sensitivity.
• Built-in test switch.
• Low standby current.
• Built-in tamper-resistant feature.
• Designed for direct surface or electrical box mounting.
• 360° field viewing angle of the visual alarm LEDs.
• Insect-resistant screening (0.020"/0.508 mm openings).
• Easy plug-in of the head to base.
• SEMS screws for easy wiring.
• Optional recess mounting.
• Field-adjustable sensitivity.

Applications

Use to contribute to life safety, fire protection, and property

conservation. Superior to photoelectric detectors in detecting

fast-flaming fires. Superior to bipolar detectors in avoiding

false alarms.

Construction & Operation

All 400 Series plug-in ionization smoke detectors contain a

unique dual-source, dual unipolar chamber detection design

which will sense the presence of smoke particles produced by

fast combustion as well as slow smoldering fires. Additional

key features include a blinking LED standby status indicator,

an easily visible alarm indication, and provision for convenient

field test and metering.
The back of the detector is sealed to block back-pressure air

flow. The chamber is protected by a fine mesh (0.020"/0.508

mm) screen to minimize problems with dust, dirt, and insects.

If cleaning is required, it is easy to remove the cover (with a

special tool) and obtain access to the screen and chamber to

perform a thorough cleaning.

Installation

Model 1451 detectors are intended for use with Notifier UL-

listed control panels. Maximum number of detectors per zone

is listed in the installation manual for each control panel. Easy

to install and maintain, this detector is designed for direct sur-

face mounting (using one of the B400 Series bases listed

below). Easy-to-wire screw terminals allow fast and simple

field wiring of IN, OUT, and remote annunciator connections.
Consult Notifier control panel specifications for the maximum

allowable loop resistance for the particular control panel to be

used.
To prevent wiring mistakes, observe polarities and make cer-

tain that each conductor is identifiable. A copy of Installation

and Maintenance Instructions is packaged with each detec-

tor. For further information, refer to NFPA 72 “Standard on

Automatic Fire Detectors.”
A Mounting Base Selection Guide is included on page 2 of

this document.

Junction Box Selection Guide

: Box depth is contingent on

base and wire size. Refer to National Electrical Code or local

applicable codes for appropriate recommendations. Bases
B401

and B401B can utilize a single-gang, 3-1/2" (88.9 mm)

octagonal, 4" (101.6 mm) octagonal, or 4" square junction box.

Bases B402B and B406B can utilize a single-gang, 3-1/2"

octagonal, 4" octagonal, 4" square, 50 mm, 60 mm, or 75 mm

junction box. Base B404B can utilize a 4" octagonal or 4"

square junction box.

General Specifications

Operating voltage: mounting base dependent (see chart

below).
Standby current: 120 micro amps.
Sensitivity: 1.9% nominal.
Weight: 0.6 pounds (272 grams).
Size: 3.2" (81.28 mm) high; 4.0" (101.6 mm) diameter with

unflanged bases, or 6.2" (157.48 mm) diameter with flanged

bases.
Construction: Flame-retardant white Noryl® plastic.
Temperature: 32°F to 120°F (0°C to 49°C).

1451

Ionization Detector shown with B401B Base

11