Notifier XP10-M 10 User Manual

Xp10-m(a), Ten-input monitor module, General

Advertising
background image

DN-6923:B • 05/15/2009 — Page 1 of 2

XP10-M(A)

Ten-Input Monitor Module

Addressable Devices

DN-6923:B • H-352

General

The XP10-M ten-input monitor module is an interface
between a control panel and normally open contact devices
in intelligent alarm systems such as pull stations, security
contacts, or flow switches.

The first address on the XP10-M is set from 01 to 150 and
the remaining modules are automatically assigned to the
next nine higher addresses. Provisions are included for dis-
abling a maximum of two unused addresses.

The supervised state (normal, open, or short) of the moni-
tored device is sent back to the panel. A common SLC input
is used for all modules, and the initiating device loops share a
common supervisory supply and ground — otherwise each
monitor operates independently from the others.

Each XP10-M module has panel-controlled green LED indi-
cators. The panel can cause the LEDs to blink, latch on, or
latch off.

NOTE: Unless otherwise specified, the term XP10-M is used in
this data sheet to refer to both the XP10-M and the XP10-MA
(ULC-listed version)

.

Features

• Listed to UL Standard 864, 9th edition.

• Ten addressable Class B or five addressable Class A initi-

ating device circuits.

• Removable 12 AWG (3.31 mm²) to 18 AWG (0.821 mm²)

plug-in terminal blocks.

• Status indicators for each point.

• Unused addresses may be disabled.

• Rotary address switches.

• Class A or Class B operation.

• FlashScan® or CLIP operation.

• Flexible mounting options.

• Mounting hardware included.

Specifications

Standby current: 3.5 mA (SLC current draw with all
addresses used; if some addresses are disabled, the
standby current decreases).

Alarm current: 55 mA (assumes all ten LEDs solid ON).

Temperature range: 32°F to 120°F (0°C to 49°C) for UL
applications; –10°C to +55°C for EN54 applications.

Humidity: 10% to 85% noncondensing for UL applications;
10% to 93% noncondensing for EN54 applications.

Dimensions: 6.8" (172.72 mm) high x 5.8" (147.32 mm)
wide x 1.25" (31.75 mm) deep.

Shipping weight: 0.76 lb. (0.345 kg) including packaging.

Mounting options:

– CHS-6 chassis: Up to 6 modules.

– BB-25 cabinet: Up to 6 modules.

– BB-XP cabinet: One or two modules.

– CAB-4 Series cabinet: See DN-6857.

– EQ Cabinet Series: See DN-60229.

Wire gauge: 12 AWG (3.31 mm²) to 18 AWG (0.821 mm²).

Power-limited circuits must employ type FPL, FPLR, or
FPLP cable as required by Article 760 of the NEC.

XP10-M is shipped in Class B position; remove shunt for
Class A operation.

Maximum SLC wiring resistance: 40 or 50 ohms, panel
dependent.

Maximum IDC wiring resistance: 1500 ohms.

Maximum IDC voltage: 10.2 VDC.

Maximum IDC current: 240 µA.

Agency Listings and Approvals

The listings and approvals below apply to the XP10-M(A) Ten-
Input Monitor Module. In some cases, certain modules or
applications may not be listed by certain approval agencies, or
listing may be in process. Consult factory for latest listing
status.

•

UL Listed: S635

•

ULC Listed: S635 (XP10-MA)

•

CSFM approved: 7300-0028:219

•

FM approved

•

MEA approved: 43-02-E

• Maryland State Fire Marshal approved: Permit #2106

6923

xp1

0.jp

g

Advertising