Agency listings and approvals, Product line information, Mounting base selection guide – Notifier 1451 4-Wire User Manual

Page 2

Advertising
background image

Page 2 of 4 — DN-1154:A • 6/4/08

Humidity range: 10 to 93% R.H. (non-condensing).
Maximum air velocity: 1,200 feet per minute (6 meters per

second).

Agency Listings and Approvals

These listings and approvals apply to the modules specified in

this document. In some cases, certain modules or applications

may not be listed by certain approval agencies, or listing may

be in process. Consult factory for latest listing status.

UL Listed: S911

ULC Listed: S911 (1451A)

MEA Listed: 427-91-E Vol. III

• FM Approved

CSFM: 7271-1653:108

BSA: 1202-88-SA

Maryland State Fire Marshal Certificate: #2185

Product Line Information

1451: Ionization Detector. Must be mounted to one of the

B400 Series Bases listed below.
RA400Z: Remote Annunciator for 2- or 4-wire applications.

Use with any System Sensor 400 Series plug-in detector. Fits

standard U.S. single-gang electrical box.
MOD400R: Field Test module for all of the System Sensor

400 Series Smoke Detectors.

B404B Wiring Diagram

5578d3.wmf

B401(B) Wiring Diagram

5578d1.wmf

B402B Wiring Diagram

5578d4.wmf

B406B Wiring Diagram

5578d2.wmf

1154d1.tif

Mounting Base Selection Guide

* Functionality contingent on panel compatibility.

** Must be limited by control panel.

Relay Contact Ratings: Resistive or Inductive (60% power factor load). Form-a: 2.0A at 30VAC/DC.

Form-C: 0.6A at 110VDC, 2.0A at 30VDC, 1.0A at 125 VAC.

(A) = ULC model designation.

Base

Model

Number

(A)

Version

Loop

Type

Current

Limit

Resistor

Alarm

Contact

Type

Nominal

Voltage

Standby

Voltage

Current

Draw on

Alarm

B401 &
B401B (A)

UL/ULC/
EN-54

2-wire*

No

-

12/24 VDC

8.5 to 35
VDC

10 to 100
mA**

B402B (A)

UL & ULC

4-wire

Yes

Form-A & -C

24 VDC

17 to 32
VDC

14 to 39
mA

B404B (A)

UL & ULC

4-wire

Yes

Form-A & -C/A
Supervisory

120 VAC

120 VAC

75 mA AC
maximum

B406B (A)

UL/ULC/
EN-54

2-wire*

No

Form-C

24 VDC

15 to 32
VDC

12 to 100
mA**

Location of

holes to

access and

release

locking

prongs.

Locking

prongs.

Cover and

screen are

removable

for cleaning.

Advertising