6. The front of the unit must be kept clear to avoid restriction of air supply for

combustion.

7. The installation must conform with the Local Codes, with the National Fuel Gas Code ANSI Z223.1,

a. The appliance and its individual shutoff valve must be disconnected from the gas supply pip-

ing system during any pressure testing of that system at test pressures in excess of 1/2 psig.

b. The appliance must be isolated from the gas supply piping system by closing its individual

manual shutoff valve during any pressure testing of the gas supply piping system at test pres-

sures equal to or less than 1/2 psig.

8. Local Regulations governing gas appliance installations must be complied with.

9. Equipment should be under a hood with adequate ventilation.

10. Installation should be in noncombustible locations only. Minimum clearances from combustible

and noncombustible construction are 6 inches from sides and back.

11. Appliance area must be free and clear of combustibles. Materials such as wood, compressed paper

and plant fibers that will ignite and burn must not be exposed near this unit. Local Safety codes

should be complied with in respect to fire avoidance.

12. This unit must be installed with adequate clearance for servicing and proper installation.

13. Provision must be made for adequate air supply.

14. Use of the supplied pressure regulator is mandatory. For SR-18 wiith front manifold refer to no. 15.

15. SR-18 FRONT MANIFOLD UNITS ONLY: This appliance has a gas manifold designed for battery

installation with interconnected manifold and is not factory supplied with a gas pressure regula-

tor. The purchaser of this equipment must obtain at time of installation a regulator suitable for

battery application, and adjustable for an outlet pressure appropriate for the manifold pressure on

the appliance. This regulator shall:

a) be listed by a nationally recognized testing agency.

b) have maximum regulation capacity for the total connected load.

c) be adjustable to the manifold pressure indicated on the rating plate.

d) Unless the manifold pressure of all connected appliances is the same,

a separate regulator must be supplied for each unit(s) to indicate unit

or units having differing manifold pressures.

16. Check that gas valve on unit is in "OFF" position (lever handle horizontal) before turning shut-off

valve "ON". Check for gas leaks using soapy water or some other suitable leak

detector. Do Not Use Open Flame For Testing.