6.2.2 Configuration of the dip-switches

When the dip-switch rocker (SW) is up it

represents the value 1 (ON) while if it is

down it represents the value 0 (OFF).

Once the configuration cover is opened the dip-

switches will appear as shown in figure.

DIP2

DIP3

DIP1

Fig. 17

6.2.3 Protocol configuration

The protocol must be set to NETWORK in

case of versions with digital video encoder (

6.2.3 Protocol configuration, page 16).

To set the protocol operate on DIP 3.
Video positioning systems of the P&T can be

controlled by a range of protocols.

PROTOCOL CONFIGURATION (DIP 3)

SW 1 SW 2 SW 3 SW 4 Configuration
OFF

ON

ON

OFF

NETWORK

Tab. 6

7 Switching on

The automatic pre-heating (De-Ice) process

could be started whenever the device is

switched on and the air temperature is

below 0°C. This process is used to ensure

that the device works properly even at

low temperatures. The duration ranges

between 60 and 120 minutes, depending

on conditions.

The unit is switched on by simply connecting the

power supply. To switch off the unit disconnect the

power.

7.1 Before powering the device

Make sure that the unit and other

components of the installation are closed

so that it is impossible to come into contact

with live parts.

Make sure that all parts are fastened down

firmly and safely.