Installation

Typical
Gas Train
Assembly
400,000 BTU/Hr
and Under

Flame Rod

Pilot

Spark Rod

Burner

Pilot Tube

Union

Modulating Valve

Manual Pilot Valve

Combination Gas Valve with
Main & Pilot Regulator

Main Manual
Gas Valve

*

A heater having an input over
400,000 BTU/Hr shall have
provisions for measuring gas
pressure between the valves,
except for heater incorporating
a single safety shut-off valve
with valve seal over travel
interlock. (ANSI Z83.4)

Flame Rod

Pilot

Spark Rod

Burner

Pilot Tube

Union

Manual
Firing Valve

Modulating
Valve

Pilot
Regulator

Pilot
Valve

Manual Pilot
Valve

Main Manual
Gas Valve

Main
Regulator

Main
Operating
Valves

Safety Shut-off
Valve

Pilot Gas Pressure Tap

* A manifold pressure tap
needs to be provided
at the burner to check
manifold pressure

*

Typical Gas
Train Assembly
400,000 BTU/Hr
and Above

Figure 5a - Gas Train Assemblies

Typical Gas Train Assembly

Figure 4 - Installation in a Duct

Elbow Duct Limits

Minimum Straight
Run 1-1/2 x "A"

Duct Height "A"

3 Ft. Minimum

Minimum Straight
Run 2 x "B"

3 Ft. Minimum

Duct Width "B"

Air Flow

Air Flow

Profile Plate

Profile Plate