Ashcroft GC35 - Pressure Sensor User Manual

Page 2

Advertising
background image

2

1. Measurement Mode is entered when applying power to the unit – LED displays

applied pressure.

2. Available “Measurement Mode” functions:

A.

Zero Adjustment: Press MODE / # keys together

Ն 3 seconds. This initiates

automatic zero adjustment; ADJ briefly appears on LED display and then returns
to Measurement Mode.

B.

Peak / Bottom (Min. Max.) Hold Display: Displayed as $ or # keys are held
for more than 3 seconds and display shows PE+. Values are reset when power
is restored to the unit, or:
Reset Peak: Hold $ key, then press # key
Reset Bottom: Hold # key, then press $ key

C.

Key Lock: Prevents overwriting values / tampering – can not be reset by restor-
ing power.
Lock: Press MODE and $ keys together; Lo( appears on LED display for 1 second.
Unlock: Press MODE and $ keys together; UnL appears on LED display for 1
second.

3. Function Setting Mode: Used for product settings, except comparator-switch set-

ting. Accessed by pressing MODE key for more than 3 seconds (complete menu
attached).
A.

Comparator Selection: Select ‘Hysteresis’ (kYS) or ‘Window Comparator’ (Yn).
Hysteresis: Switch remains activated until reset point has been achieved.
Window Comparator: Switch activates each time pressure enters a set ‘pres-
sure band’ determined by the A and B settings.

B.

Comparator Operation Selection: Select nPn or PnP. Note: LED ring is Blue
with nPn and Green with PnP.

C.

Filter Dampening Setting: This is based upon a moving average of pressure
data to reduce display “bounce” and smooth analog output due to system pres-
sure fluctuations. User configurable with five selections:
25ms, 250ms, 2.5s, 5s and 10s.
Filter will not be applied if 0 is selected.

D.

Power-Save (Energy-Saving) Setting: Product is equipped with automatic
LED display turn-off feature. User may elect to turn-on display when reading
pressure or using as an indicating instrument.

E.

LED Ring Feature Setting: Turns Red when comparator-switch is ON and Blue
(nPn) or Green (PnP) when comparator-switch is OFF.

F.

Display Unit Setting: User may alter unit of measures from standard to arbitrary.

G.

Display Settings: Allows for decimal point adjustment.

H.

Analog Output Scaling: Available with only 1 comparator; function sets analog
output for pressures corresponding to Zero (4mA) and Span (20mA) adjustment
in percentage figures.
Analog output under zero point pressure: After A-L is displayed, select the per-
centage corresponding with the current analog output value under Zero (4mA)
using
# or $ keys – when pressure range displayed is set to 0.0-100.0% FS.
Analog output under span point pressure: After A-K is displayed, select the per-
centage corresponding with the current analog output value under Span (20mA)
using
# or $ keys – when pressure range displayed is set to 0.0-100.0% FS.

Example 1)

Example 2)

PRESSURE RANGE (%F.S.)

A

N

A

L

O

G

O

U

P

U

T

(m

A

d

c

)

-100

-50

0

50

100

150

20

16

12

8

4

PRESSURE RANGE (%F.S.)

A

N

A

L

O

G

O

U

P

U

T

(m

A

d

c

)

-100

-50

0

50

100

150

20

16

12

8

4