background image

4

4. Comparator-Switch / Loop Check Mode: Access by pressing MODE for less

than 3 seconds.
A.

Comparator-Switch Setting: To activate / deactivate comparator-switch,
scroll to US1 (4-20mA version only) or US2 and select USE / noU. Enter com-
parator-switch set point by selecting A-1 or A-2 and use #/$ keys for pres-
sure setting. Now enter ‘deadband’ value (pressure difference between set
and reset values) by selecting b-1 or b-2 and use #/$ keys for setting. Note:
unit automatically configures the reset point. Increasing setpoint is entered as
a positive ‘deadband’ value, while decreasing setpoint is entered as a negative
‘deadband’ value.

B.

Loop Check: Allows the user to check comparator-switch operation without
requiring pressure input. Use $ or # keys to view comparator-switch function
in a simulated test of the application.

Comparator-Switch Setting / Loop Check Menu

P5I

Function Setting Mode

Filter Setting

Decimal Point Position

Display Unit Setting

Select Comparator Mode

LED Ring Feature Setting

Comparator Operation

Selection

Measurement Mode

Press 3 sec.

or longer

Press 3 sec.

or longer

MODE

MODE

MODE

MODE

MODE

MODE

MODE

MODE

MODE

MODE

MODE

MODE

After 1 second

kY5

kY5

!;n

Select with

X W

keys

Select with

X W

keys

Select with

X W

keys

Message displayed

Current setting

Hysteresis

Window comparator

After 1 second

OP(

npn

npn

pnp

Message displayed

Current unit

setpoint

NPN output

PNP output

Select with

X W

keys

EoF

Eon

Power-save OFF

Power-save ON

e(O

Message Display

Current Setting

e(O

eOf

After 1 second

f;l

f-1

Message displayed

Current setting

After 1 second

lRg

Message Display

Current Setting

L

lRI

After 1 second

Select with

X W

keys

ET[

P5I

psi, bar or mPa

Display Scaling

UN;

Message Display

Current Setting

u

After 1 second

Select with

X W

keys

Power-save setting

(Display Scaling)

Set Offset Value

(Display Scaling Set)

Full Scale Value

Pressure when the

analog is at zero point

Pressure when the

analog is at span point

f-0

Filter off

f-1

Time constant 25ms

f-2

Time constant 250ms

f-3

Time constant 2.5s

f-4

Time constant 5s

f-5

Time constant 10s

Select with

X W

keys

Set Any Desired Position Within the

–100 to 150% range with the

X W

keys

Set Any Desired Position Within the

–100 to 150% range with the

X W

keys

X W

Key to Select Between
(–)1999~(+)9999

X W

Key to Select Between
(–)1999~(+)9999

0

0.0

0.000

0.00

Lr0

No LED interlock

Lr1

Comparator 1 is

interlocked with LED

Lr3

Comparator 1 & 2 are

interlocked with LED

Lr2

Comparator 2 is

interlocked with LED

d-p

Message Display

Current Setting

d

0.00

After 1 second

d-l

Message Display

Current Setting

d

0.00

After 1 second

d-K

Message Display

Only in Output Selection

Display Scaling

Current Setting

d

0.00

After 1 second

A-L

Message Display

Current Setting

a

0.0

After 1 second

a

Message Display

Current Setting

a-k

100.0

After 1 second

D I S P L AY S E T T I N G

A N A LO G O U P U T S CA L I N G

(n

~P