Us1 use use nou, Sav 5-i 5-i 5-2, A-1 5.00 – Ashcroft GC35 - Pressure Sensor User Manual

Page 3: On1 0.00, B-1 1.00, Of1 0.00, Us2 use use nou, A-2 5.00, On2 0.00, B-2 1.00

Advertising
background image

3

Notes: Values shown are from the example within the complete I&M manual.

Changes made in the Setting Mode are saved by returning to Measurement
Mode before powering off the unit.

Comparator Setting Mode

Loop Check Mode

Measurement Mode

Press less
than 3 sec.

(In Case of Intact)

(In Case of Intact)

(In Case of Analog Output)

Press 3 sec.

or longer

MODE

MODE

Comparator 1 Use/No Use

MODE

After 1 second

US1

USE

USE

noU

Select with

X W

keys

Message displayed

Current setting

In use

Not in use

Setting Storage of Comparator

MODE

After 1 second

Sav

5-I

5-I

5-2

Message displayed

Storage Area Indication

Storage Area 1

Storage Area 2

Comparator 1 Setting Point A

MODE

After 1 second

A-1

5.00

Message displayed

Current setting

X W

set any desired value within the

–1999 to 9999 range with UP/Down keys

MODE

Comparator 1 ON Delay

After 1 second

on1

0.00

Message displayed

Current setting

X W

set any desired value within the

0 to 2 sec range with UP/Down keys

Comparator 1 Setting Point B

After 1 second

b-1

1.00

Message displayed

Current setting

X W

set any desired value within the

–1999 to 9999 range with UP/Down keys

MODE

MODE

Comparator 1 OFF Delay

After 1 second

oF1

0.00

Message displayed

Current setting

X W

set any desired value within the

0 to 2 sec range with UP/Down keys

Select

X W

keys/reading by long pushing

Select

X W

keys/reading by long pushing

Comparator 2 Use/No Use

MODE

After 1 second

US2

USE

USE

noU

Select with

X W

keys

Message displayed

Current setting

In use

Not in use

Comparator 2 Setting Point A

MODE

After 1 second

A-2

5.00

Message displayed

Current setting

X W

set any desired value within the

–1999 to 9999 range with UP/Down keys

MODE

Comparator 2 ON Delay

After 1 second

on2

0.00

Message displayed

Current setting

X W

set any desired value within the

0 to 2 sec range with UP/Down keys

Comparator 2 Setting Point B

After 1 second

b-2

1.00

Message displayed

Current setting

X W

set any desired value within the

–1999 to 9999 range with UP/Down keys

MODE

MODE

Comparator 1 OFF Delay

After 1 second

on2

0.00

Message displayed

Current setting

X W

set any desired value within the

0 to 2 sec range with UP/Down keys

MODE

Loop Check Mode

After 1 second

Lop

7.52

Message displayed

Before mode shift

setting value

X W

key to select an arbitrary number

between -10 to 110%F.S. of the current
dispaly unit for simulating the pressure

Setting Loading of Comparator

MODE

After 1 second

Lod

L-1

L-1

l-2

Message displayed

Storage Area Indication

Storage Area 1

Storage Area 2

Function Setting Mode Menu