Bonding  the  cabinet  to  the  telecommunications  ground  

Z4-­‐Series  SeismicFrame  Cabinets  should  be  bonded  to  the  telecommunications  ground.    The  top  panel,  

side  panels,  doors  and  mounting  rails  on  the  Z4-­‐Series  SeismicFrame  cabinet  are  electrically  bonded  to  

the  frame.    A  ground  strap  bonds  the  side  panels  and  doors  to  the  frame.    Nibs  screws  bond  the  top  

panel  to  the  frame.    In  order  to  bond  the  cabinet  to  the  telecommunications  ground,  use  the  Ground  

Terminal  Block  (included)  to  connect  a  bonding  conductor  to  the  telecommunications  ground  or  signal  

reference  grid.    Remove  the  mask  sticker  at  desired  grounding  location  and  apply  generous  coating  of  

gray  antioxidant.    Secure  grounding  wire  to  the  terminal  block.    Attach  the  block  to  the  cabinet  frame  

with  an  8  mm  wrench  using  two  M5  bolts  and  nuts.      

 

 

 

 

 

 