Intended  Use  

 

Keep  a  printed  copy  of  the  Preface  of  this  User’s  Manual  in  or  near  the  cabinet.    

 

•  Install  the  cabinet  only  in  a  Restricted  Access  Location,  such  as  a  data  center.  

•  Use  indoors  only,  in  environmentally  controlled  areas;  do  not  use  outdoors,  in  harsh  environments,  

or  in  air-­‐handling  spaces.    

•  Use  the  cabinet  for  information  technology  and  telecommunications  equipment,  including  servers  

and  peripherals.    

•  Allow  only  qualified  service  personnel  to  use  the  cabinet.    

•  The  cabinets  must  be  anchored  to  the  floor  to  ensure  stability  and  a  safe  working  environment.  

•  The  load-­‐bearing  capacity  of  the  Z4-­‐Series  SeismicFrame  Cabinet  is:    

 

 

Static:      

3,000  lb  (1360  kg)*  

Seismic:  

1,500  lb  (680  kg)**  

 

 

*Tested  to  UL  2416,  Issue  2,  July  2013  Section  11.1.4,  Loading  test  (4X  rated  load)  

 

**Tested  to  Telcordia  Technologies  GR-­‐63-­‐CORE,  Issue  4,  April  2012,  Sections  4.4  

 

 

 