11

the PV system. Battery charging is managed by a constant volt-
age PWM algorithm that has been optimized for PV systems.
The only manual tasks performed by the operator are:

a. Installation (see Section 5.3 )
b. Battery type selection (see Section 5.3-7)
c. Maintenance (see Section 6.3)

6.2

O

PERATION AND

F

UNCTIONS

The PV system operator should become familiar with the fol-
lowing operating functions and design of the SunSaver con-
troller. Refer to the Technical Specifications (Section 8.0) for
actual setpoints and other parameter values.

• 100% Solid State

All power switching is done with FETs. No mechanical relays

are used in the controller.

• Battery Charge Regulation

SunSaver uses an advanced series PWM charge control for

constant voltage battery charging. A true 0 to 100% PWM

duty cycle is very fast and stable for positive charge control

under all system conditions.

• Temperature Compensation

A sensor next to the green LED measures ambient temp-

erature conditions. The SunSaver corrects the constant

voltage setpoint –28 (–56 for 24V) mV per °C with a 25°C

reference. This correction matches the battery charging

to the changing electrochemical properties of the battery,

and works best if the battery and controller are in a similar

thermal environment.

• Sealed / Flooded Select

Flooded batteries require more vigorous charging to avoid

stratification, and sealed batteries require precise control to

avoid outgassing. The SunSaver constant voltage setpoints

are 14.4 (or 28.8) volts for flooded batteries, and 14.1 (or

28.2) volts for sealed batteries. See Section 5.3-7 for more

information.

• LED Indicators