The following instructions set the sensor enable line high long enough for the
SR50 to detect it, then set it low.

1: Set Port (P20)
1: 1

Set

High

2: 1

Port

Number


2: Excitation with Delay (P22)
1: 1

Ex

Chan

2: 1

Delay w/Ex (units = 0.01 sec)

3: 0000

Delay After Ex (units = 0.01 sec)

4: 0.0

mV

Excitation


3: Set Port (P20)
1: 0

Set

Low

2: 1

Port

Number


The P3 instruction counts the pulse train being transmitted from the SR50.
Distance-to-surface will automatically be reset to 0.00 after the distance is
calculated and stored for later processing and output.

4: Pulse (P3)
1: 1

Reps

2: 1

Pulse

Input

Chan

3: 00

Config

Option

4: 21

Loc [ Dis2Surf ]

5: -.0025 Mult
6: 0.0

Offset


Measure air temperature and convert to degrees Kelvin. This example assumes
air temperature is being measured with Campbell Scientific’s Model 107
probe.

5: Temp 107 Probe (P11)
1: 1

Reps

2: 1

In

Chan

3: 1

Excite all reps w/Exchan 1

4: 22

Loc [ T_Kelvin ]

5: 1

Mult

6: 273.15 Offset


Compute the air temperature compensation factor and correct the distance-to-
surface for air temperature (see formula 1).

6: Z=F (P30)
1: 273.15 F
2: 23

Z Loc [ 273_15 ]


7: Z=X/Y (P38)
1: 22

X Loc [ T_Kelvin ]

2: 23

Y Loc [ 273_15 ]

3: 24

Z Loc [ ATempComp ]