SR50 Sonic Ranging Sensor

16

If Flag 2 is high, compute the air temperature compensation factor and correct
the distance-to-surface measurement for air temperature (see Formula 1).

3: If Flag/Port (P91)
1: 12

Do if Flag 2 is High

2: 30

Then

Do


4: Z=F (P30)
1: 273.15 F
2: 23

Z Loc [ 273_15 ]


5: Z=X/Y (P38)
1: 22

X Loc [ T_Kelvin ]

2: 23

Y Loc [ 273_15 ]

3: 24

Z Loc [ ATempComp ]


6: Z=SQRT(X) (P39)
1: 24

X Loc [ ATempComp ]

2: 24

Z Loc [ ATempComp ]


7: Z=X*Y (P36)
1: 21

X Loc [ Dis2Surf ]

2: 24

Y Loc [ ATempComp ]

3: 21

Z Loc [ Dis2Surf ]


Add distance-to-ground to distance-to-snow (which is negative) to calculate
snow depth.

In the following instruction, Parameter 2 is a constant. You enter the distance-
to-ground at your site.

8: Z=X+F (P34)
1: 21

X Loc [ Dis2Surf ]

2: 2.0

F

3: 25

Z Loc [ Temporary ]


Move snow Depth to another location so that it can be viewed.

9: Z=X (P31)
1: 25

X Loc [ Temporary ]

2: 10

Z Loc [ SnowDepth ]


10: Do (P86)
1: 22

Set Flag 2 Low


11: End (P95)


Measure the sensor every 15 minutes by setting Flag 1 high.