SR50 Sonic Ranging Sensor

17

Parameter 2 of P92 determines how often to measure.

12: If time is (P92)
1: 0

Minutes

into

a

2: 15

Minute

Interval

3: 11

Set Flag 1 High


13: If Flag/Port (P91)
1: 11

Do if Flag 1 is High

2: 30

Then

Do


Enable the sensor by pulsing Control Port 1.

14: Set Port (P20)
1: 1

Set

High

2: 1

Port

Number


15: Excitation with Delay (P22)
1: 1

Ex

Chan

2: 1

Delay w/Ex (units = 0.01 sec)

3: 0000

Delay After Ex (units = 0.01 sec)

4: 0.0

mV

Excitation


16: Set Port (P20)
1: 0

Set

Low

2: 1

Port

Number


17: Do (P86)
1: 21

Set Flag 1 Low


18: Do (P86)
1: 12

Set Flag 2 High


19: End (P95)


This is an example or an Hourly output array, yours may vary.

20: If time is (P92)
1: 0

Minutes

into

a

2: 60

Minute

Interval

3: 10

Set Output Flag High


21: Real Time (P77)
1: 0220

Day,Hour/Minute (prev day at midnight, 2400 at midnight)


22: Sample (P70)
1: 1

Reps

2: 10

Loc [ SnowDepth ]*


End Program