Campbell Scientific TDR100 Time Domain Reflectometry Systems User Manual

Page 45

Advertising
background image

TDR100

;{CR10X}
;
;Program Name = T100EX#1
;

*Table 1 Program
01: 60

Execution

Interval

(seconds)


;Measure the datalogger power supply voltage:

1: Batt Voltage (P10)
1: 1

Loc [ Bat_Volt ]


;Measure the internal temperature of the datalogger:

2: Internal Temperature (P17)
1: 2

Loc [ DL_Temp ]


;Set port 5 high to switch ON "Switched 12V" power from the datalogger to power the TDR100.

3: Do (P86)
1: 45

Set Port 5 High


;Measure the CS610 probe connected directly to the TDR100 and convert to water content:

4: TDR100 Measurement (P119)
1: 0

SDM

Address

2: 0

La/L

3: 0000

MMMP Mux & Probe Selection

4: 4

Waveform

Averaging

5: 1

Vp

6: 250

Points

7: 5.75

Cable

Length

(meters)

8: 5

Window

Length

(meters)

9: .3

Probe

Length

(meters)

10: 0.085

Probe

Offset

(meters)

11: 3

Loc [ WC_1 ]

12: .1138

Mult

; Multiplier for Liedu Calibration

13: -0.1758 Offset

; Offset for Liedu Calibration


;Turn off the switched 12V to power off the TDR100:

5: Do (P86)
1: 55

Set Port 5 Low


;Set the Output Flag to output data every 5 minutes:

6: If time is (P92)
1: 0

Minutes (Seconds --) into a

2: 5

Interval (same units as above)

3: 10

Set Output Flag High (Flag 0)