External connection – APC SILCON 10-40KW 400V UPS User Manual
Page 20
 
20
Installation Guide APC Silcon 10-40kW 400V UPS
990-4050
External Connection
The built-in parallel board connects two or more UPS systems in parallel, either to obtain 
increased system reliability or to obtain higher output power. The parallel board also ensures 
correct load-sharing between paralled systems.
To prepare the UPS for parallel/redundant mode, disconnect all sources of AC and DC power 
supply to the UPS and connect the ribbon cable from the parallel board to the main controller 
board (the ribbon cable is delivered with the UPS).
Complete the parallel system set-up by connecting the external control cables (see below). 
Follow the instructions in the “Programming Parameters for Advanced Parallel” section of this 
guide to execute necessary re-programming. 
NOTICE!
For reliability reasons, APC recommends separate battery packs in redundant/parallel 
conigurations.
CAUTION!
DO NOT connect ribbon cable between controller and parallel card in single configurations. 
Ribbon cable is for parallel operation only.