Programming parameters – APC SILCON 10-40KW 400V UPS User Manual
Page 53
 
Programming Parameters
990-4050
Installation Guide APC Silcon 10-40kW 400V UPS
53
5.3.2 Programming example
Example with four systems in parallel with separate batteries.
•
Programme the station addresses 1-4: 1 for UPS 1, 2 for UPS 2, 3 for UPS 3, and 4 for 
UPS 4.
•
All UPS systems have to be programmed to “Highest station address”:4.
•
If APM is not to be tested, “APM test mode active” must be “NO”.
•
If a system is isolated due to service, the station numbers must be reprogrammed for the 
remaining active systems starting with number 1 and ending with maximum. number 
of active systems. No number must be left in this sequence. Furthermore, “Highest 
station address” must be changed to number of active UPSs in parallel.
5.4
Battery Monitor
5.4.1 Installation of new batteries
To avoid false alarms, the above procedure MUST be followed.
NOTICE!
Contact your local dealer if you have any questions regarding changing parameters.