Appendix, 0 appendix, 1 table 1. installation planning data – APC SILCON 10-40KW 400V UPS User Manual
Page 88

88
Installation Guide APC Silcon 10-40kW 400V UPS
990-4050
Appendix
9.0 Appendix
9.1
Table 1. Installation Planning Data
Main Input
Breaker
Field
Wiring*
Battery Bank**
UPS Module
Service Bypass Panel
Field
Wiring
Output
Breaker
*
** Internal Batteries available for 40kW units and smaller
*
*
Q1
Q2
Q3
* Not supplied by APC
Installation Planning Data
APC Silcon Series
AC Input
Battery System DC
AC Output
Min. Input
Input
Full
I
Nom
I
Max
Load side
Heat
Power rating
Source
P (kW)
I (A)
Cable
Overcurrent
V
n
load
Disch Disch
I
n
Overcurrent Dissipation
kW
kVA
Pf
V
Hz
Nom.
Max.
Nom.
Max.
(per phase)
Protection*
(Vdc)
P(kW)
(A)
(A)
(A)
Protection*
(kW)
10
10
1
380
400
415
50/60
11.2
13.0
17.7
17.0
16.3
19.5
18.7
17.9
4mm
2
20 A
2x384
10.8
14
16
15.2
14.5
13.9
16 A
0.54
20
20
1
380
400
415
50/60
22.2
25.7
35.3
33.7
32.4
38.8
37.1
35.6
10mm
2
40 A
2x384
21.5
28
33
30.3
29.0
27.8
32 A
0.94
40
40
1
380
400
415
50/60
43.9
50.9
69.8
66.7
64.0
76.8
73.4
70.4
16mm
2
80 A
2x384
42.2
55
65
60.6
58.0
55.6
63 A
1.5
COLUMN
1a
1b
1c
1d
1e
1f
1g
1h
2a
2b
2c
2d
3a
3b
4a
NOTES
3
4
1
2
9
5, 6, 13
8
12
10
11
6, 7
13
* Provided by others