4 airflow direction, 1 vertical airflow – Panasonic CS-XE9PKUA User Manual

Page 35

Advertising
background image

35

OD Pipe Temperature

A 78.8°F

(26°C)

B 91.4°F

(33°C)

š During above condition, when indoor heat exchanger temperature is below 41°F (5°C), the outdoor fan will stop

according to outdoor piping temperature as following:

12.4 Airflow Direction

š There are two types of airflow, vertical airflow (directed by horizontal vane) and horizontal airflow (directed by

vertical vanes).

š Control of airflow direction can be automatic (angles of direction is determined by operation mode, heat

exchanger temperature and intake air temperature) and manual (angles of direction can be adjusted using
remote control).

12.4.1 Vertical

Airflow

Operation Mode

Airflow Direction

Upper Vane Angle (°)

Lower Vane Angle (°)

1 2 3 4 5 1 2 3 4 5

Heating

Auto with Heat

Exchanger

Temperature

A 25

17

B 55

37

C 25

17

Summer House

55

37

Manual

20 45 55 65 70 17 27 37 47 56

Cooling

Auto

45 ~ 70

2 ~ 39

Manual

20 25 50 55 70 2 7 17 27 39

Soft Dry

Auto

45 ~ 70

2 ~ 39

Manual

20 25 50 55 70 2 7 17 27 39


1. Automatic vertical airflow direction can be set using remote control; the vane swings up and down within the

angles as stated above. For heating mode operation, the angle of the vane depends on the indoor heat
exchanger temperature as Figure 1 below. It does not swing during fan motor stop. When the air conditioner is
stopped using remote control, the vane will shift to close position.

2. Manual vertical airflow direction can be set using remote control; the angles of the vane are as stated above and

the positions of the vane are as Figure 2 below. When the air conditioner is stopped using remote control, the
vane will shift to close position.