12.4.2 Horizontal

Airflow

š The horizontal airflow direction louvers can be adjusted manually by hand.

12.5 Quiet operation (Cooling Mode/Cooling area of Dry Mode)

š Purpose

o

To provide quiet cooling operation compare to normal operation.

š Control

condition

o

Quiet operation start condition

ƒ

When “POWERFUL/QUIET” button at remote control is pressed twice.

POWERFUL/QUIET LED illuminates.

o

Quiet operation stop condition

ƒ

When one of the following conditions is satisfied, quiet operation stops:

š POWERFUL/QUIET button is pressed again.

š Stop by OFF/ON switch.

š Timer “off” activates.

š AUTO COMFORT button is pressed.

š ECONAVI button is pressed.

ƒ

When quiet operation is stopped, operation is shifted to normal operation with previous setting.

ƒ

When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.

ƒ

When operation mode is changed, quiet operation is shifted to quiet operation of the new mode.

ƒ

During quiet operation, if timer “on” activates, quiet operation maintains.

ƒ

After off, when on back, quiet operation is not memorised.

š Control

contents

o

Fan speed is changed from normal setting to quiet setting of respective fan speed.

Fan speed for quiet operation is reduced from setting fan speed.

12.6 Quiet Operation (Heating)

š Purpose

o

To provide quiet heating operation compare to normal operation.

š Control

condition

o

Quiet operation start condition

ƒ

When “POWERFUL/QUIET” button at remote control is pressed.

POWERFUL/QUIET LED illuminates.

o

Quiet operation stop condition

ƒ

When one of the following conditions is satisfied, quiet operation stops:

š POWERFUL/QUIET button is pressed again.

š Stop by OFF/ON switch.

š Timer “off” activates.

š AUTO COMFORT button is pressed.

š ECONAVI button is pressed.

ƒ

When quiet operation is stopped, operation is shifted to normal operation with previous setting.

ƒ

When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.

ƒ

When operation mode is changed, quiet operation is shifted to quiet operation of the new mode, except

fan mode only.

ƒ

During quiet operation, if timer “on” activates, quiet operation maintains.

ƒ

After off, when on back, quiet operation is not memorised.

š Control

contents

o

Fan speed manual

ƒ

Fan speed is changed from normal setting to quiet setting of respective fan speed.

ƒ

Fan speed for quiet operation is reduced from setting fan speed.

o

Fan Speed Auto

ƒ

Indoor FM RPM depends on pipe temp sensor of indoor heat exchanger.