Rectifier alarms, User’s guide, Network management card – APC Network Management Card AP9617 User Manual

Page 51

Advertising
background image

®

USER’S GUIDE

network management card

49

From the

Rectifiers

sub-menu, type

2

for configurable

Rectifier Alarms

:

Rectifier Alarms

Description

1- High Voltage
Alarm

The alarm action that occurs if the High Voltage Threshold has
been violated. See

Rectifier Parameters

.

Allowed values: any standard alarm selection

a

.

2- Low Voltage
Alarm

The alarm action that occurs if the Low Voltage Threshold has been
violated. See

Rectifier Parameters

.

Allowed values: any standard alarm selection

a

.

3- Configuration
Alarm

The alarm action that occurs if a new rectifier is detected that was
not present when the system was rebooted or powered on.

Allowed values: any standard alarm selection

a

.

4- 1 of N Alarm

The alarm action that occurs if one rectifier fails in a DC Power
Plant with multiple rectifiers

Allowed values: any standard alarm selection

a

.

5- 2 of N Alarm

The alarm action that occurs if two or more rectifiers fail.

Allowed values: any standard alarm selection

a

.

6- Diagnostic
Alarm

The alarm action that occurs in response to a diagnostic alarm for
the rectifier controller.

Allowed values: any standard alarm selection

a

or n of N

b

.

7- Imbalance
Alarm

The alarm action that occurs for rectifier imbalance.

Allowed values: any standard alarm selection

a

or n of N

b

.

a

Standard alarm selections:

Major

activates the major relay.

Minor

activates the minor relay.

Relay 1

through

Relay 6

activates the relay specified.

Ignore

ignores the alarm.

b

n of

N

activates the alarm setting for menu item 4 (1 of N) if one rectifier fails, or

activates the alarm setting for menu item 5 (2 of N) if two or more rectifiers fail.