Batteries: Status, Thresholds and Alarms

From

Device Manager

, type

1

to select

DC Power Plant

. Then type

4

to

select

Batteries

. The following options are displayed.

1- Battery Status
2- Battery Thresholds
3- Battery Alarms

Battery Status.

From the

Batteries

sub-menu, type

1

for

Battery Status

:

Menu Item

Description

Float Voltage (V)

The DC Power Plant voltage, in volts. To set this value, see

Battery Thresholds

.

Maximum Recharge (A)

The battery maximum recharge rate, in amps. To set this
value, see

Battery Thresholds

.

Amp/Hour Capacity (AHr)

Battery amp-hour size. To set this value, see

Battery

Thresholds

.

Compensation Temp
Coefficient (mV/degC/cell)

Compensation temperature coefficient, in millivolts. To set this
value, see

Battery Thresholds

.

High Knee Temperature
(0V/degC/cell)

The temperature (in Celsius) above which Float Voltage no
longer changes to compensate for increase in temperature. To
set this value, see

Battery Thresholds

.

Low Knee Temperature
(0V/degC/cell)

The temperature (in Celsius) below which Float Voltage no
longer changes to compensate for decrease in temperature. To
set this value, see

Battery Thresholds

.

Current (A)

The battery current, in amps.

Temperature

The battery temperature, in degrees Celsius.

Current Sane

Indicates, by

yes or no, whether battery current is within an

acceptable range.

Temperature Sane

Indicates, by

yes or no, whether battery temperature is within

an acceptable range.