Power Plant Alarms/Internal Log

From

Device Manager

, type 1 to select

DC Power Plant

. Then type 7 to

select

Power Plant Alarms/Internal Log

. The following options are

displayed:

1- Power Plant Status

2- Power Plant Internal Log

Alarm Status.

From the

Power Plant Alarms/Internal Log

sub-menu,

type

1

for

Power Plant Status

to display the status of all DC Power Plant

alarms.

Interpret an alarm status item as follows:

• For the meaning of each active alarm status item, see the descriptions

of the alarms displayed on the Control Unit menus, as listed in your DC
Power Plant product manual.

• The last character of an alarm item is one of the following:

– The number of the relay that the alarm has activated

– m for a minor alarm

– M for a major alarm

In the following example, item 1 indicates that the System Low Voltage
Alarm is on and is a major alarm, item 3 indicates the System Low
Temperature Alarm is on and is a minor alarm, and item 4 indicates that the
Battery Low Voltage alarm is on and has activated relay 2.

1: Sys LV Alm On M

2: Load LV Alm On M

3: Sys LT Alm On m

4: Batt LV Alm On 2

5: Hdwr Batt T Alm 4