Control terminal connections, Operation – Beijer Electronics Industrial Inverter E2 User Manual

Page 16

Advertising
background image

16

4.11.

Control Terminal Connections

Default Connections

Control

Terminal

Signal

Description

1

+24V User Output,

+24V, 100mA.

2

Digital Input 1

Positive logic
“Logic 1” input voltage range: 8V … 30V DC
“Logic 0” input voltage range: 0V … 4V DC

3

Digital Input 2

4

Digital Input 3 /

Analog Input 2

Digital: 8 to 30V
Analog: 0 to 10V, 0 to 20mA or 4 to 20mA

5

+10V User Output

+10V, 10mA, 1kΩ minimum

6

Analog Input 1 /

Digital Input 4

Analog: 0 to 10V, 0 to 20mA or 4 to 20mA
Digital: 8 to 30V

7

0V

User ground connected terminal 9

8

Analog Output /

Digital Output

Analog: 0 to 10V, 20mA maximum
Digital: 0 to 24V

9

0V

User ground connected terminal 7

10

Relay Common

11

Relay NO Contact

Contact 250Vac, 6A / 30Vdc, 5A

Advertising