Mechanical Mounting

-

Information can be found
on page 10

Keypad operation can be
found on page 17

Motor Cable Sizes

-

Check the rating
information on page 28

-

For EMC compliance, use
a shielded type cable

-

Motor Connections

-

Check for Star or Delta connection
according to the motor voltage rating
(See page 13)

Motor Nameplate Details

-

Enter the motor rated voltage in P-07

-

Enter the motor rated current in P-08

-

Enter the motor rated frequency in P-09

Fuses

or MCB

Earth L N
L1 L2 L3

AC Supply Voltage

(50 / 60Hz)

Supply Voltage :

-

110-115, 200-240, 400-
480 +/- 10%

-

1 or 3 Phase

-

Check the drive rating
information on page 28

Fuses or MCB, Cable Sizes :

-

Fuse Ratings given on page
28

-

Recommended cable sizes
shown on page 28

Always follow local and national
codes of practice

IP66 Easy Start-Up Guide

(Un-switched Variant)

RJ45
Connector

Control Terminals
Based on the factory default (out of box)
settings

-

Connect a Start / Stop switch
between terminals 1 & 2

-

Close the switch to Start (Enable)
the drive

-

Open the switch to Stop (Disable)
the drive

-

Connect a potentiometer (5kΩ
minimum) between terminals 5, 6
and 7 as shown below to vary the
speed from minimum (0Hz) to
maximum (50 / 60 Hz)