HT Series ECM Blower Performance Data

Airfl ow in CFM with wet coil and clean air fi lter

Residential

Units Only

Model

Max
ESP

(in. wg)

Fan

Motor

(hp)

Range

Cooling Mode

Dehumid

Mode

Heating Mode

Fan

Only

Mode

Aux/

Emerg

Mode

Stg 1

Stg 2

Stg 1

Stg 2

Stg 1

Stg 2

026

1.0

1/2

Default

700

525

550

425

750

600

350

850

Maximum

1000

800

800

600

1000

850

1000

1000

Minimum

600

450

550

400

600

450

300

700

038

0.9

1/2

Default

1050

800

850

650

1100

850

550

1350

Maximum

1500

1100

1200

900

1500

1100

1500

1500

Minimum

900

600

825

550

900

600

450

1350

049

1.0

1

Default

1400

1050

1100

850

1500

1150

700

1500

Maximum

2000

1500

1600

1200

2000

1500

2000

2000

Minimum

1200

900

1100

825

1200

900

600

1350

064

0.7

1

Default

1750

1300

1400

1050

1875

1450

875

1875

Maximum

2300

1900

2000

1500

2300

1900

2300

2300

Minimum

1500

1100

1375

1000

1500

1100

750

1500

072

0.7

1

Default

1900

1450

1650

1250

2000

1650

950

2000

Maximum

2300

2200

2000

1800

2300

2200

2300

2300

Minimum

1800

1350

1650

1250

1800

1350

900

1800

During Auxiliary operation (residential units only) the CFM will run at the higher if the heating (delay jumper) or AUX settings

Airfl ow is controlled within +/- 5% up to Max ESP shown with wet coil and standard 1” fi berglass fi lter

Do not select Dehumidifi cation mode if HP CFM is on setting 1

All units AHRI/ISO/ASHRAE 13256-1 rated HP (Cooling) Delay (Heating) CFM Setting 3

Note: See the ECM Blower Control section for information on setting taps.